DCRACK

Specifications 1Set 36kW 47U Rack Space I for Air-cooling Servers
Price
20,000 $/Unit
Product Glance     Value
Model DCRACK
Version V1
Capacity 47U
Maximum load,kW 36
PUE@25℃ ambient, 25℃ air supply(1-1) 1.17
Supply air temperature for classic server,  18~27℃
Detailed Characteristics     Value
Part 1: Server Cabinet     Value
Hardware Configuration
Size (Length*Width*Height), mm (without package) 1,600*1,200*2,350
Size (Length*Width*Height), mm (with package) 1,720*1,300*2,400
Net weight, kg (without package) 668
Gross weight, kg (with package) 686
Network connection mode RJ45 Ethernet 10/100M
Power Supply
Power supply AC Input voltage, Volt(2-1) 380~415 AC
Power supply AC Input Frequency Range, Hz 50~60
Maximum Power supply AC Input current, Amp(2-2) 63
Fan
Rated power, W 2,500
Noise, dBA@1m 85
Size (Length*Width* Thickness), mm 378*378*375
Number of fans 3
Part 2: External Cooler Value
Hardware Configuration
Size (Length*Width*Height), mm (without package) 1,896*1,026*2,180
Size (Length*Width*Height), mm (with package) 2,000*1,130*2,360
Net weight, kg (without package) 396
Gross weight, kg (with package) 414
Power Supply
Power supply AC Input voltage, Volt(2-1) 380~415V AC
Power supply AC Input Frequency Range, Hz 50~60
Maximum Power supply AC Input current, Amp(2-2) 63
Heat pump
Rated power, kW 8.5
COP (typical) 4.75
Refrigerant R410A
Fan
Rated power, kW 1.85
Noise, dBA@1m 82
Size (Length*Width* Thickness), mm 805*805*211
Number of fans 2
Refrigerant pump
Rated power, W 550
Flow rate, m3/h 1
Pump head, m 48
Size (Length*Width* Height), mm 420*152*202
Environment requirements Value
Ambient temperature, °C -20~45℃
Installation distance (max), m(2-3) 50
Storage temperature, °C -20~70
Operation humidity(non-condensing), RH 10~90%

Reviews

There are no reviews yet.

Be the first to review “DCRACK”

Your email address will not be published. Required fields are marked *